Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T07EL01243
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/12/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07EL01243 7/5/07 and 7/12/07 1. For abandoned electrical service entrance conductors and electrical services, indicate so on the plans. 2. Provide location of panel/s to be powered from the new service, on a scaled drawing. 3. If 200A panel is new, for future use, please state so on the plans. If existing, please state so on the plans. Clarify intent. 5. Provide fault current rating of all new equipment. 6. Provide fault calculations. 7. Provide job address on all sheets. |