Permit Number: T07EL01051
Parcel: 124140720

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T07EL01051
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07EO01051 7/6/07

1. Grounding Electrode Conductor shall be sized at 1/0, not #4. Reference NEC Table 250.66.
2. Provide TEP Available Fault Current and Fault Current Rating of new Equipment.
3. For a one-family dwelling, the minimum size Service Disconnecting Means, is 100A, not 60A. Reference NEC 230.79 (C). per jackie is a 100a disc w/60a cb.