Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T07EL01051
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/09/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07EO01051 7/6/07 1. Grounding Electrode Conductor shall be sized at 1/0, not #4. Reference NEC Table 250.66. 2. Provide TEP Available Fault Current and Fault Current Rating of new Equipment. 3. For a one-family dwelling, the minimum size Service Disconnecting Means, is 100A, not 60A. Reference NEC 230.79 (C). per jackie is a 100a disc w/60a cb. |