Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T07EL00934
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07el00934 6/6/07 1. Put address on large font plans. 2. Indicate conductor sizes on feeders. Conductors shall be protected according to the requirements of NEC 240 and NEC Table 310.16 75ÂșC column. 3. Show grounding electode system and sizing of grounding electrode conductor. 4. Provide TEP available fault current. 5. Provide fault current rating of new equipment. 6. Provide fault calculations for existing panels. 7. Provide location of TEP pole and distance from new service. |