Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/15/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07EL00879 5/15/07 1. Indicate Keynote 3 on Power Plan. 2. If the existing power was overhead, indicate such on the plans. Otherwise apply for a Waiver. 3. Address available fault current and fault current rating on Panel A. 4. Indicate which electrical loads are intended for Panel A. |