Permit Number - T07EL00678
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/20/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | ELECTRICAL COMMENTS, THE FOLLOWING PALN HAS BEEN DENIED FOR THE FOLLOWING REASONS 1. IN ORDER TO DETERMINE IF A #4 BC GROUNDING ELECTRODE CONDUCTOR IS OF SUFFICIENT SIZE FOR THE TOTAL SERVICE, IT IS REQUIRED TO KNOW THE SIZE OF THE SERVICE ENTRANCE CONDUCTORS IN THE GUTTER. 2.THE SIZE OF THE SERVICE ENTRANCE CONDUCTORS IS REQUIRED FOR AMPACITY DETERMINATION OF SERVICE TO ADD LOAD. 3. ADDRESSES ARE REQUIRED FOR INDIVIDUAL UNITS AND OWNERS METER ON APPLICATION, THIS IS FOR CLEARANCE TO TEP. 4.THE SERVICE WILL ALSO REQUIRE A WATER AND GAS BOND IF AVAILABLE ON SITE . 5. PROVIDE INFO ON FIXTURE TYPE IT MUST BE SHIELDED. RAY MAJUTA ELECT PL CK DSD 520/837-4891 11/21/07 |