Permit Number: T07EL00678
Parcel: 13109144C

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T07EL00678
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied ELECTRICAL COMMENTS, THE FOLLOWING PALN HAS BEEN DENIED FOR THE FOLLOWING REASONS

1. IN ORDER TO DETERMINE IF A #4 BC GROUNDING ELECTRODE CONDUCTOR IS OF SUFFICIENT SIZE FOR THE TOTAL SERVICE, IT IS REQUIRED TO KNOW THE SIZE OF THE SERVICE ENTRANCE CONDUCTORS IN THE GUTTER.
2.THE SIZE OF THE SERVICE ENTRANCE CONDUCTORS IS REQUIRED FOR AMPACITY DETERMINATION OF SERVICE TO ADD LOAD.
3. ADDRESSES ARE REQUIRED FOR INDIVIDUAL UNITS AND OWNERS METER ON APPLICATION, THIS IS FOR CLEARANCE TO TEP.
4.THE SERVICE WILL ALSO REQUIRE A WATER AND GAS BOND IF AVAILABLE ON SITE .
5. PROVIDE INFO ON FIXTURE TYPE IT MUST BE SHIELDED.
RAY MAJUTA
ELECT PL CK DSD
520/837-4891
11/21/07

Final Status

Task End Date Reviewer's Name Type of Review Description
11/26/2007 VFLORES1 OUT TO CUSTOMER Completed
11/26/2007 VFLORES1 REJECT SHELF Completed