Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07EL00415
Parcel: 10821029C

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T07EL00415
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/29/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07EL00415 2/29/08

1. Provide a scaled drawing with all equipment.
2. Put the address on all sheets of the plans.
3. Add Engineering, Zoning, and Fire to WrokFlow.
4. Provide voltage, amperage, phase, and fault current rating of service and panel.
5. Provide TEP available fault current.
6. Provide legible drawings.
7. Provide a grounding electrode system, and sizing for grounding electrode conductor.