Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T07EL00415
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/29/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07EL00415 2/29/08 1. Provide a scaled drawing with all equipment. 2. Put the address on all sheets of the plans. 3. Add Engineering, Zoning, and Fire to WrokFlow. 4. Provide voltage, amperage, phase, and fault current rating of service and panel. 5. Provide TEP available fault current. 6. Provide legible drawings. 7. Provide a grounding electrode system, and sizing for grounding electrode conductor. |