Review Date Reviewer's Name Type of Review Description Status Comments
02/29/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07EL00415 2/29/08

1. Provide a scaled drawing with all equipment.
2. Put the address on all sheets of the plans.
3. Add Engineering, Zoning, and Fire to WrokFlow.
4. Provide voltage, amperage, phase, and fault current rating of service and panel.
5. Provide TEP available fault current.
6. Provide legible drawings.
7. Provide a grounding electrode system, and sizing for grounding electrode conductor.