Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T07EL00140
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/05/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t07el00140 3/5/07 1. Provide site plan with all equipment, including tie-in to existing UG pullbox. 2. Indicate number of services disconnects already on the building, and voltage/phase. 3. Provide marking to indicate that this new service only powers North Access Pole Lights. 4. Provide overcurrent protection for the #8 conductor. 5. Provide available fault current at new service, and fault current rating of new service disconnect and overcurrent protective device(s). |