Permit Number: T07EL00140
Parcel: 128010190

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T07EL00140
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07el00140 3/5/07
1. Provide site plan with all equipment, including tie-in to existing UG pullbox.
2. Indicate number of services disconnects already on the building, and voltage/phase.
3. Provide marking to indicate that this new service only powers North Access Pole Lights.
4. Provide overcurrent protection for the #8 conductor.
5. Provide available fault current at new service, and fault current rating of new service disconnect and overcurrent protective device(s).