Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T07EL00089
Parcel: 11005317A

Address:
3071 N SWAN RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T07EL00089
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/17/2007 MICHAEL ST. PAUL ZONING REVIEW Passed