| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/30/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07CM04868 4/24/08 1. Add specifications for new pullchain lights in new storage rooms. Need to know wattage and type of fixture and lamp. 2. Document date of Revision 2 on Sheet E.2. 3. Panel A, at 49761VA, would draw 207A, overloading the 200A panel. This was missed on first review. |