Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Permit Number - T07CM04864
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2008 | ANDREW CONNOR | NPPO | REVIEW | Passed | |
| 01/22/2008 | SUNRISE ENGINEERING | 2ND PARTY REVIEW | REVIEW | Denied | CITY OF TUCSON - FIRST CHECK City of Tucson Nos. T07CM04863 & T07CM04864 Sunrise Job Nos. 02648.0034 & 02648.0035 January 22, 2008 City of Tucson 201 N. Stone Ave. Tucson, Arizona 85726 Re: Plan Review: O’Neill-Scurry Residence and Detached Garage Address: 2240 East Greenlee Road #1 Sunrise Engineering’s Building & Safety Team has completed a first review of the following documents on behalf of the City of Tucson Development Services Department: 1. Plans: Two (2) copies (24 sheets, A-0 – E-3) dated December 28, 2007 by Lanning Architecture. 2. Structural Calculations: Two (2) copies dated December 22, 2007 by Copper Creek Engineering Co. and one (1) copy completed, signed and sealed City of Tucson special inspection certificate dated December 28, 2007 by Copper Creek Engineering Co. 3. Truss Drawings: None provided (deferred). 4. Geotechnical (Soils) Report: Two (2) copies geotechnical engineering evaluation dated July 30, 2007, Project Number 07-248 by Pattison-Evanoff Engineering, L.L.C. 5. Other: Two (2) copies each: Letter requesting deferred submittal of trusses dated December 26, 2007 by Lanning Architecture; specifications sheet, Napoleon BGD42CF direct vent gas fireplace; REScheck compliance certificate and accompanying inspection checklist dated December 28, 2007 by Lanning Architecture; specification for SPJ lighting light fixture SPJ36-11; specification for Bilco window well system; ICC ES evaluation report ESR-1269 for AMVIC ICF; specifications sheets for AMVIC and Mikey Block ICF. Deferred Submittals: Documents for deferred submittal items shall be submitted, reviewed and approved in accordance with IBC Section 106.3.4.2 or IRC Section R802.10, as applicable. Note that deferred submittals are required for the following: Prefabricated wood trusses. Special Inspections: Note that special inspection in accordance with IBC Section 1704 is required for the following: ICF wall construction and reinforcing steel placement, concrete embedments. These documents were reviewed only for their conformance to the provisions of the applicable adopted codes, including the City of Tucson amended 2006 International Residential Code (IRC) and the City of Tucson/Pima County Outdoor Lighting Code. Our comments follow on the attached list. Please submit an itemized response letter and the required number of complete and revised documents with all revisions clouded. Sincerely, SUNRISE ENGINEERING, Building & Safety Team Gary R. Goodell, C.B.O., Senior Plans Examiner, I.C.C. Plans Examiner GRG:grg Enclosures BUILDING SUMMARY (SQ. FT.): NEW DETACHED SINGLE-FAMILY DWELLING (T07CM04863): Livable Area, Basement: 585 Livable Area, 1st Story: 2,585 Livable Area, 2nd Story: 1,478 Total Livable: 4,648 Covered Porches: 1,268 (includes 2nd-story balcony) Total Under Roof, Dwelling 5,916 Uncovered Roof Deck and Stairs: 483 NEW DETACHED GARAGE (T07CM04864): Garage: 944 The following plan review comments are based on the City of Tucson’s building codes and, unless otherwise noted, refer to the 2006 International Residential Code (IRC) as amended and adopted by the City of Tucson, and the City of Tucson/Pima County Outdoor Lighting Code. Please respond in writing to each comment by marking the following comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance. The following code comments reflect a review of building plans only. If site-related comments are applicable to this project, they will be generated by others (e.g., Planning, Engineering, Public Works, Health, etc.). GENERAL COMMENTS: 1. Sheet A-1, M-1 and/or P-2, Manufacturer’s Installation Instructions. Please add a note stating that manufacturer’s installation instructions, as required by the IRC for items such as gas fireplaces, gas logs and other listed appliances or components, shall be available on the construction site at the time of inspection. Reference IRC Section R106.1.2. 2. Automatic Fire Sprinklers. Please coordinate with the local fire department having jurisdiction as to whether an automatic fire sprinkler system is required to be installed as required under certain circumstances by Appendix L of the IRC as adopted and amended by the City of Tucson. This is simply a reminder and does not require a response. 3. Additional Review Comments. Due to the fact that additional information is being requested for the second review, there may be additional review comments. ARCHITECTURAL COMMENTS: 1. Sheets A-2 and A-3, Windows. Window 28 is not shown on the south elevation and window 30 is not listed in the window schedule. 2. Sheets A-0 and A-1, Minimum Glazed Openings. The basement is included as part of the “livable” area in the project information listed on Sheet A-0. As such, it may be considered to be habitable area requiring natural light and ventilation in accordance with IRC Section R303.1. Please provide either evidence that the basement is not habitable area subject to Section R303.1 or revise the plans to either provide glazed openings complying with Section R303.1 or provide mechanical ventilation and artificial light in accordance with Exceptions 1 and 2 to Section R303. Reference IRC Sections 106.1.1 and R303.1. 3. Sheets A-1 through A-3, Safety Glazing. Please specify that approved safety glazing is to be provided in windows 8 and 28, which are located in shower and tub enclosures, and in windows 9 and 26, which are located in bathrooms containing a shower or tub. Reference IRC Sections R308.4(5.) and ARS § 36-1631. 4. Sheet A-1, Under Stair Protection. Please revise the plans to confirm that the enclosed accessible space under the stairs is to have walls, under stair surface and any soffits protected on the enclosed side with ½” gypsum board. Reference IRC Section R311.2.2. 5. Sheet A-10, Stair Headroom. Detail 12 includes a note stating that the minimum headroom is to be 6 ft. 1 3/16 inches. Please add to or revise a note to confirm that the minimum headroom requirement is 6 ft. 8 inches. Reference IRC Section R311.5.2. 6. Sheets A-1, A-2, A-10 and/or A-13, Riser Height and Tread Width. Please add a note and/or detail stating that the maximum allowable riser height is 7 ¾ inches, that the minimum tread depth is 10 inches and that the variation within the stair run is not to exceed 3/8-inch. Reference IRC Sections R311.5.3.1 and R311.5.3.2. 7. Sheets A-1, A-2 and A-13, Handrail, Stair to Roof Deck. Please revise the plans or add a note or detail confirming that a handrail is to be provided at the exterior stairs to the roof deck in accordance with IRC Section R311.5.6. 8. Sheets A-3 through A-5, Guards. Please clarify that the minimum guard height is to be at least 36 inches and that, if open guards are to be installed, the openings may not allow the passage of a 4-inch-diameter sphere. See IRC Section R312 for details. 9. Sheet A-7 or A-14, Field Treatment. Please add a note stating that field cut ends, notches and drilled holes of pressure preservatively treated wood are to be retreated in the field in accordance with AWPA M4. Reference IRC Section R320.1.2. 10. Sheet A-0 or A-3, Premises Identification. Please add a note stating that approved numbers or addresses are to be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Reference IRC Section R321. 11. Sheet A-7 or A-8, Fireblocking. Please add a note and/or details stating that fireblocking is to be provided to cut off all concealed draft openings (both vertical and horizontal) and to form an effective barrier between a story and the roof space. Fireblocking is to be provided in the following locations: In concealed spaces of stud walls, including furred spaces and parallel rows of studs or staggered studs, vertically at ceiling and floor levels, and horizontally at intervals not exceeding 10 feet. At all interconnections between concealed vertical and horizontal spaces such as occur at soffits, drop ceilings and cove ceilings. At openings around vents, pipes and ducts at ceiling and floor level. Chimney fireblocking. All spaces between chimneys and floors and ceilings through which chimneys pass shall be fireblocked with noncombustible material securely fastened in place. Reference IRC Sections R602.8 and R1001.16. 12. Sheet A-11, Ceiling Gypsum Board. Details 1, 2 and 9 show that ½-inch gypsum board is to be applied on some of the ceilings. If this is to occur where the framing is 24 inches on center, please add a note and/or detail showing that the ½-inch board is to be the sag-resistant type. Reference IRC Table R702.3.5, foot note d. 13. Sheet A-11, Flashing. Please add a note and/or details confirming that approved corrosion-resistant flashing is to be provided at all of the following locations: -At the top of all exterior window and door openings; -At the intersection of chimneys or other masonry construction with frame or stucco walls; -Under and at the ends of masonry, wood or metal copings and sills; -Continuously above all projecting wood trim; -Where exterior porches, decks or stairs, attach to a wood frame wall or floor assembly; -At wall and roof intersections; -At built-in gutters. Reference IRC Section R703.8. 14. Sheet A-1, Alternate Unvented Roof. A note on Sheet A-1 refers to “Roof Design Detail #5,” but this detail does not appear to be shown on the plans. Detail #5, as approved by the Greater Tucson Area Building Officials, is for “TJI” roof framing and also includes a number of other criteria, including a light colored roof and additional mechanical fresh-air requirements. Please provide the applicable and complete details that have been approved by the Greater Tucson Area Building Officials. Reference IRC Sections R104.11, R106.1.1 and R806. 15. Sheet A-9, Roof Drains And Scuppers. Please provide a scupper detail, including the size of the scupper, for the scupper that is to drain the roof area above the Master Bedroom and also revise the plans to show how drainage is to be provided for the roof deck area. Reference IRC Sections R106.1.1 and R903.4 and the Plumbing Code. 16. Sheet A-11, Roof Covering Type And Application And Attachment. A note on this sheet states only that a “clay tile roof” is to be used. Please provide notes and/or details confirming that the roof covering type and its application and attachment comply with IRC Sections 904 and 905. If applicable, provide an evaluation report or other listing approval for the concrete tile roof covering system. Reference IRC Sections R904 and R905. STRUCTURAL COMMENTS: This portion has been reviewed and accepted. ENERGY EFFICIENCY COMMENTS: 1. REScheck Software Edition. The RES-check certificate that has been submitted appears to show that the structure meets or exceeds IRC requirements, but it states that it is an earlier version, Version 3.6, and thus may not meet the requirements of the 2006 editions of the IRC and IECC. The most current version, available for free download at http://www.energycodes.gov/rescheck/, is Version 4.0.1, dated January 2007. MECHANICAL, PLUMBING AND ELECTRICAL COMMENTS: 1. Sheet P-2, Gas-Fired Barbecue. Please add a note stating that the BBQ is to be listed for its purpose, including outdoor installation, and that its installation is to be in accordance with its listing, including required clearances to combustible materials. Reference IRC Sections G2406.3 and G2447.1. 2. Sheet P-1, Gray Water Notes. For coordination purposes, it appears that the City of Tucson Waste Water Utility requires additional information to be added to the plans regarding the proposed gray water system. 3. Sheet E-1, Wall Receptacles. Please add an additional receptacle outlet at the wall space that is two (2) feet or wider in the Kitchen to the left of Door 2. Reference IRC Section E3801.2. 4. Sheet G-1, Additional Locations. Please revise the electrical plan to add a switched light fixture outside of the swinging exterior door to the garage. Reference IRC Section E3803.3. 5. Sheets E-1, E-2 and G-1, Disconnecting Means. Please revise the electrical plan to show that a disconnect is to be provided near and in sight of mechanical equipment, including air conditioning condensing units and heat pump units. Reference IRC Section E4001.5 and Table 4001.5. OUTDOOR LIGHTING CODE COMMENTS: 1. Sheet E-1, Floodlight Aiming. Please add a note stating that floodlights are to be aimed no higher than 45 degrees to the horizontal (halfway between straight down and straight to the side) when the source is visible from any adjacent residential property. Reference note 6, Table 401.1, 2006 City of Tucson/Pima County Outdoor Lighting Code. If you have any questions regarding the above comments, please contact Gary Goodell at (480) 768-8600, extension 136, between 8:00 A.M. and 5:00 P.M., Monday through Friday. |
| 01/24/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Needs Review | |
| 02/04/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/04/2008 | SUE REEVES | OUT TO CUSTOMER | Completed |