| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/07/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET C-1: TITLE BLOCK INDICATES (2) STRUCTURES? CLARIFY WHY THIS WAS INKED IN. 2. SHEET S-2 PLAN; CALCULATION PAGE 7: PLAN INDICATES C8 X 2.5 X 14 GAGE PURLIN WHILE CALCULATIONS CALL OUT C10 X 2.5 X 14 GAGE PURLIN. CLARIFY. 3. SHEET S-2 PLAN; CALCULATION PAGE 23: VERIFY NO ROOF BRACING REQUIRED BETWEEN GRIDS 1 AND 2. SHOULD AN ADDITIONAL CABLE BRACE PER DETAIL 3/S-2 BE ADDED AT GRID 2? 4. SHEET S-1; CALCULATION PAGE 37: PLAN INDICATES 2'-6" SQUARE X 3'-6" DEEP FOOTING AT TYPE 2 WHILE CALCULATIONS CALL OUT 3'-6" SQUARE X 2'-6" DEEP FOOTING. CLARIFY. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/29/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 04/29/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 04/29/2008 | GERARDO BONILLA | REJECT SHELF | Completed |