Permit Number: T07CM04836
Parcel: 110090240

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM04836
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. SHEET C-1: TITLE BLOCK INDICATES (2) STRUCTURES? CLARIFY WHY THIS WAS INKED IN.
2. SHEET S-2 PLAN; CALCULATION PAGE 7: PLAN INDICATES C8 X 2.5 X 14 GAGE PURLIN WHILE CALCULATIONS CALL OUT C10 X 2.5 X 14 GAGE PURLIN. CLARIFY.
3. SHEET S-2 PLAN; CALCULATION PAGE 23: VERIFY NO ROOF BRACING REQUIRED BETWEEN GRIDS 1 AND 2. SHOULD AN ADDITIONAL CABLE BRACE PER DETAIL 3/S-2 BE ADDED AT GRID 2?
4. SHEET S-1; CALCULATION PAGE 37: PLAN INDICATES 2'-6" SQUARE X 3'-6" DEEP FOOTING AT TYPE 2 WHILE CALCULATIONS CALL OUT 3'-6" SQUARE X 2'-6" DEEP FOOTING. CLARIFY.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2008 DELMA ROBEY APPROVAL SHELF Completed
04/29/2008 DELMA ROBEY OUT TO CUSTOMER Completed
04/29/2008 GERARDO BONILLA REJECT SHELF Completed