Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04829
Parcel: 10511061R

Address:
4500 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM04829
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM04829 12/26/07

1. Provide overcurrent protection for ALL feeders per NEC Article 240.
2. Indicate voltage levels and phase on plans.
3. Ampacity of 500 MCM Al is 310A, which exceeds load.
4.Transformer secondary conductors are in violation of NEC 240.21 (C) (4) (2).
5. Provide conduit and conductor size for transformer primary and secondary.
6. Provide size on Grounding Electrode conductor for feeder to new disconnect, and feeders to trailers.
7. Provide House Panel Load calculations.