01/28/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM04829 12/26/07

1. Provide overcurrent protection for ALL feeders per NEC Article 240.
2. Indicate voltage levels and phase on plans.
3. Ampacity of 500 MCM Al is 310A, which exceeds load.
4.Transformer secondary conductors are in violation of NEC 240.21 (C) (4) (2).
5. Provide conduit and conductor size for transformer primary and secondary.
6. Provide size on Grounding Electrode conductor for feeder to new disconnect, and feeders to trailers.
7. Provide House Panel Load calculations.