Permit Number: T07CM04829
Parcel: 10511061R

Address:
4500 N ORACLE RD

Review Status: Completed

Review Details: MODULAR BUILDINGS

Permit Number - T07CM04829
Review Name: MODULAR BUILDINGS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2008 DAVE MANN FIRE REVIEW Approved
01/08/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/26/2007 RONALD BROWN PLUMBING-COMMERCIAL REVIEW Passed
12/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04829 12/26/07

1. Indicate disconnecting means at trailers. Reference NEC 225.31, 225.32.
2. Provide overcurrent protection for trailer feeders per NEC Article 240.
3. Provide location of Panel TR, transformer, fused disconnect, and existing House Panel, on plans. Plans Examiner to check per NEC 240.21 when this has been done.
4. Provide panel schedule for Panel TR and load calculations.
5. Provide conduit and conductor size for transformer primary and secondary.
6. Provide size on Grounding Electrode conductor for transformer.
7. The Equipment Grounding Conductor between the existing circuit breaker and the new fused disconnect should be sized at #2, not #4. Reference NEC 250.122 (B).
8. Provide House Panel Load calculations.
12/26/2007 HEATHER THRALL ZONING REVIEW Approved
12/26/2007 LOREN MAKUS ENGINEERING REVIEW Approved
12/26/2007 RBROWN1 WATER REVIEW Passed
12/26/2007 RONALD BROWN MECHANICAL-COMMERCIAL REVIEW Passed
12/26/2007 RBROWN1 WWM REVIEW Passed
12/26/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Passed