Permit Review Detail
Review Status: Completed
Review Details: MODULAR BUILDINGS
Permit Number - T07CM04829
Review Name: MODULAR BUILDINGS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/08/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
01/08/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
12/26/2007 | RONALD BROWN | PLUMBING-COMMERCIAL | REVIEW | Passed | |
12/26/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04829 12/26/07 1. Indicate disconnecting means at trailers. Reference NEC 225.31, 225.32. 2. Provide overcurrent protection for trailer feeders per NEC Article 240. 3. Provide location of Panel TR, transformer, fused disconnect, and existing House Panel, on plans. Plans Examiner to check per NEC 240.21 when this has been done. 4. Provide panel schedule for Panel TR and load calculations. 5. Provide conduit and conductor size for transformer primary and secondary. 6. Provide size on Grounding Electrode conductor for transformer. 7. The Equipment Grounding Conductor between the existing circuit breaker and the new fused disconnect should be sized at #2, not #4. Reference NEC 250.122 (B). 8. Provide House Panel Load calculations. |
12/26/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
12/26/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
12/26/2007 | RBROWN1 | WATER | REVIEW | Passed | |
12/26/2007 | RONALD BROWN | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
12/26/2007 | RBROWN1 | WWM | REVIEW | Passed | |
12/26/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/08/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |