Permit Number: T07CM04828
Parcel: 99999999M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04828
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: January 2, 2007
SUBJECT: Light Control Cabinet
TO: Pavex
LOCATION: 6215 S Airfield Drive
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07CM04828 (First Review)


RESUBMITTAL REQUIRED: Street Light Control Cabinet

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed street light control cabinet for the above referenced property. Engineering Division does not recommend approval of the submittal at this time. Please address the following review comments prior to the next submittal.

Street Light Control Cabinet:

1. Clearly indicate location of street light control cabinet for easy reference on next submittal.
2. Entire property appears to be located within a FEMA identified special flood hazard area. Floodplain Use Permit will be required. Provide Floodplain Use Permit with next submittal. Be advised that there is a $50.00 application fee for the Floodplain Use Permit. Permit application enclosed.
3. Provide copy of the approved drainage report for Ryan Airfield. Depth of flow required in order to establish criteria for installation of proposed light control cabinet.
Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
01/03/2008 DROBEY1 ZONING REVIEW Needs Review
01/03/2008 ROBERT SHERRY WATER REVIEW Passed
12/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Equipment Grounding Conductor for street lighting circuits should be sized at #4, not #10. Reference NEC 250.122 (B).
2. Demonstrate compliance with the Tucson Lighting Code. Please note that this appears to be in Area E 1 c.
3. For all poles greater than 20' in height, pole and foundation detail and calculations shall be prepared and sealed by a Structural Engineer registered in the State of Arizona.
12/26/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. REQUIRE CALCULATIONS FOR LIGHT POLE FOUNDATION. MUST BE SIGNED AND SEALED BY LICENSED ENGINEER.
12/27/2007 MARTIN BROWN FIRE REVIEW Approved
12/27/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/03/2008 DELMA ROBEY APPROVAL SHELF Completed
01/03/2008 DELMA ROBEY OUT TO CUSTOMER Completed
01/03/2008 DELMA ROBEY REJECT SHELF Completed