Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04828
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Denied | DATE: January 2, 2007 SUBJECT: Light Control Cabinet TO: Pavex LOCATION: 6215 S Airfield Drive REVIEWERS: Bianca Ramirez, CFM ACTIVITY: T07CM04828 (First Review) RESUBMITTAL REQUIRED: Street Light Control Cabinet SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed street light control cabinet for the above referenced property. Engineering Division does not recommend approval of the submittal at this time. Please address the following review comments prior to the next submittal. Street Light Control Cabinet: 1. Clearly indicate location of street light control cabinet for easy reference on next submittal. 2. Entire property appears to be located within a FEMA identified special flood hazard area. Floodplain Use Permit will be required. Provide Floodplain Use Permit with next submittal. Be advised that there is a $50.00 application fee for the Floodplain Use Permit. Permit application enclosed. 3. Provide copy of the approved drainage report for Ryan Airfield. Depth of flow required in order to establish criteria for installation of proposed light control cabinet. Additional comments may be forthcoming. If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov Bianca C. Ramirez Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 837-4928 office (520) 879-8010 fax |
| 01/03/2008 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 01/03/2008 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 12/26/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Equipment Grounding Conductor for street lighting circuits should be sized at #4, not #10. Reference NEC 250.122 (B). 2. Demonstrate compliance with the Tucson Lighting Code. Please note that this appears to be in Area E 1 c. 3. For all poles greater than 20' in height, pole and foundation detail and calculations shall be prepared and sealed by a Structural Engineer registered in the State of Arizona. |
| 12/26/2007 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. REQUIRE CALCULATIONS FOR LIGHT POLE FOUNDATION. MUST BE SIGNED AND SEALED BY LICENSED ENGINEER. |
| 12/27/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/27/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/03/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 01/03/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 01/03/2008 | DELMA ROBEY | REJECT SHELF | Completed |