Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM04807
Parcel: 11516019S

Address:
1375 W GRANT RD

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM04807
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/18/2008 MARTIN BROWN FIRE REVIEW Denied 1) From 2006 IFC, table 2403.12.2, exits for an occupant load of this magnitude required to be 96" wide. Verify (and show dimensions on plans) that no point inside structure is more 100' from an exit.
2) Structural calculations required for tents exceeding 10,000 square feet.
3) Also, a separate permit for tents from the fire department is required.