Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T07CM04807
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/17/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/18/2008 | MARTIN BROWN | FIRE | REVIEW | Denied | 1) From 2006 IFC, table 2403.12.2, exits for an occupant load of this magnitude required to be 96" wide. Verify (and show dimensions on plans) that no point inside structure is more 100' from an exit. 2) Structural calculations required for tents exceeding 10,000 square feet. 3) Also, a separate permit for tents from the fire department is required. |