Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM04806
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2008 MARTIN BROWN FIRE REVIEW Denied 1) Need new plans. Cover sheet has old approval stamps on it.
2) From 2006 IFC, table 2403.12.2, exits for an occupant load of this magnitude required to be 120" wide. Verify (and show dimensions on plans) that no point inside structure is more 100' from an exit.
3) Structural calculations required for tents exceeding 10,000 square feet.
4) Also, a separate permit for tents from the fire department is required.