Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T07CM04806
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/18/2008 | MARTIN BROWN | FIRE | REVIEW | Denied | 1) Need new plans. Cover sheet has old approval stamps on it. 2) From 2006 IFC, table 2403.12.2, exits for an occupant load of this magnitude required to be 120" wide. Verify (and show dimensions on plans) that no point inside structure is more 100' from an exit. 3) Structural calculations required for tents exceeding 10,000 square feet. 4) Also, a separate permit for tents from the fire department is required. |