Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04803
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/27/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04803 12/27/07 1. Series rating note implies a 4-tiered system, not available commercially. Please note that the available fault current at New Panels TN and N appears to be less than 10K. Thus the series-rating note as applied to Panel B only would be sufficient. Suggest that the wording "...and new electrical equipment..." be deleted from series-rating note. |
| 12/28/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/28/2007 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review |