Permit Number: T07CM04803
Parcel: 134210900

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04803
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/21/2007 STEVE SHIELDS ZONING REVIEW Approved
12/21/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/21/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04803 12/21/07

1. New Panel N, with 30.1A, is on a 20A circuit.
2. Total VA for Phases A, B, and C on the sub-feed to Panel TN. are 12276, 11100, and 8556 respectively, not 4080, typ. Please correct this, and re-evaluate all loads on Panel B.
3. Provide short circuit rating of panels.
4. Provide fault calculations.
12/21/2007 ROBERT SHERRY WATER REVIEW Approved
12/21/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/21/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/21/2007 DAVE MANN FIRE REVIEW Approved
12/27/2007 GERRY KOZIOL WWM REVIEW Passed
12/27/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/27/2007 CPIERCE1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/27/2007 CPIERCE1 APPROVAL SHELF Completed
12/27/2007 CPIERCE1 OUT TO CUSTOMER Completed
12/27/2007 CPIERCE1 REJECT SHELF Completed