Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04803
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/21/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/21/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/21/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04803 12/21/07 1. New Panel N, with 30.1A, is on a 20A circuit. 2. Total VA for Phases A, B, and C on the sub-feed to Panel TN. are 12276, 11100, and 8556 respectively, not 4080, typ. Please correct this, and re-evaluate all loads on Panel B. 3. Provide short circuit rating of panels. 4. Provide fault calculations. |
| 12/21/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/21/2007 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/21/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/21/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/27/2007 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 12/27/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/27/2007 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/27/2007 | CPIERCE1 | APPROVAL SHELF | Completed |
| 12/27/2007 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 12/27/2007 | CPIERCE1 | REJECT SHELF | Completed |