Permit Number: T07CM04781
Parcel: 131010260

Address:
4844 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04781
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2007 HEATHER THRALL ZONING REVIEW Approved
12/20/2007 BIANCA RAMIREZ ENGINEERING REVIEW Denied Floodplain Use Permit Required
12/20/2007 DAVE MANN FIRE REVIEW Approved
12/21/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/21/2007 JWILLIA5 ELECTRICAL-COMMERCIAL REVIEW Passed
12/21/2007 ROBERT SHERRY WATER REVIEW Approved
12/21/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. DEMO TO ADDRESS REMOVAL OF ILLEGAL TOILET REMODELING
2. JUSTIFY NUMBER OF TOILET FIXTURES PER OCCUPANT LOAD
3. MODIFY H/C STALLS TO FIT FLOOR MOUNTED WC
12/21/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water and waste & vent riser diagrams.
2. Specify how the water heater platform is to be anchored to the wall and indicate the wall construction.
12/21/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/27/2007 CPIERCE1 WWM REVIEW Completed