Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM04780
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2008 | WILDAN | 2ND PARTY REVIEW | REVIEW | Approved | |
| 04/28/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Third request. Show the size, material, and slope of the new building sewer (sheet G0.2). Reference Sections 103.2.3 and 718.1, UPC 2006. 2. Third request. Provide cleanouts in the building sewer (sheet G0.2) at intervals not exceeding 100 feet and show how they are to be installed. Reference Sections 719.1 and 719.5, UPC 2006. |
| 04/28/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/29/2008 | RBROWN1 | ADA | REVIEW | Denied | SHEET GO.1 1. SUMMARY OF GOVERNING REGULATIONS: THIS IS A CITY OF TUCSON PROJECT AND THE GOVERNING ACCESSIBILITY CODE IS ADAAG SHEET GO.2 2. NOTE 4": CHANGE 2' WIDE TRUNCATED DOMES TO 3' WIDE TRUNCATED DOMES AS PER AADAG, SECTION 4.29.5 3. PROVIDE SPOTS GRADES OF THE NEW ACCESSIBLE PARKING SPACES, AISLE AND THROUGHOUT THE ACCESSIBLE ROUTE TO SHOW COMPLIANCE WITH ADAAG SLOPE REQUIREMENTS, SECTIONS 4.6.3 AND 4.3.7 4. DENOTE PARKING SIGNAGE ON PLAN AND REFER TO SIGN DETAIL. 5. PROVIDE SIGN DETAIL AS PER TDOT, 7' ABOVE FINISHED GRADE TO BOTTOM OF SIGN WITH "VAN ACCESSIBLE" SIGN ATTACHMENT FOR SPACE IDENTIFIED. SHEET A1.1 6. DETAIL 3: ALL DIMENSIONS AND CLEARANCES TO BE AS PER ADAAG. REVISE ALL DIMENSIONS ACCORDINGLY. 7. DETAIL 2: PROVIDE DIMENSIONS SHOWING TOILET FIXTURE AND ACCESSORY CLEARANCES AS REQUIRED BY ADAAG, SECTIONS 4.13, 4.15, 4.16, 4.17, 4.19 AND 4.22. |
| 05/06/2008 | TERRY STEVENS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Terry Stevens Lead Planner PROJECT: T07CM04780 4823 S. 6th Ave ADA changes and firewall installation TRANSMITTAL DATE: 5-6-08 COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. This comment has not been addressed. The minimum width of a sidewalk is four (4) feet per DS 2-08.5.1.A. Key note #1 indicates 36". Revise note and add dimension to meet code. 2. This comment has not been addressed. Per DS 2-08.4.1 all sidewalks shall be physically separated from any vehicular use area (front of the parking spaces) by means of curbing, grade separation, barriers, railings or other means. If grade separation is used for the sidewalk a handicap ramp will be required immediately north of the landing in front of the handicap parking access aisle. 3. This comment has not been addressed. Per ANSI 117.1-2003 Sec. 502.5 the maximum slope within a handicap access aisle is 1:48. Key note #6 indicates the slope not to exceed 1:20. Revise. 4. This comment has not been addressed. Provide a detail of the required handicap parking signage, clearly indicating size, verbiage and height above grade. (min. height above grade to the bottom of the main sign is seven (7) feet). If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961 C:\planning\cdrc\DSD\T07CM04780-2.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/07/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 05/07/2008 | SHANAE POWELL | REJECT SHELF | Completed |