Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM04780
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/22/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. Reprint M1.1 so that the background is legible. Reference Section 106.3.1, IMC 2006. |
| 01/22/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Include all fixtures when calculating the total demand and determining pipe sizes (i.e. correct the arithmetic in the calculations). Reference Section 610.1, UPC 2006. 2. Comment not addressed. Calculate the water demand using the fixture units shown in Tables 6-5 or A-2 (use assembly fixture units for the water closets). Reference Section 610.3, UPC 2006. 3. Comment not addressed. Provide the rim elevation of the sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson. 4. Comment not addressed. Show the size, material, and slope of the new building sewer (sheet G0.2). Reference Sections 103.2.3 and 718.1, UPC 2006. 5. Comment not addressed. Provide cleanouts in the building sewer at intervals not exceeding 100 feet and show how they are to be installed. Reference Sections 719.1 and 719.5, UPC 2006. |
| 01/28/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide electrical power for EF-3. Reference Sheet M1.1. 2. Provide electrical power for WH-1 and WH-2. Reference Sheet P2.1. 3. Short circuit calculation, with a utility available fault current of 22,000A for this 400A commercial single-phase service, is based upon an underground secondary of at least 45' in length. The underground secondary on the plans scales out to be about 15'. 4. Short circuit calculation uses a 145' utility secondary length. The underground secondary on the plans scales out to be about 15'. 5. Short circuit calculation assumes AFC to be at the utility transformer. Per TEP SR-510 single phase available fault currents are given at the line terminals of the metering equipment. 6. It appears that this submittal is the same as the drawings reviewed 12/21/07. |
| 01/28/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 02/05/2008 | SREEVES1 | ZONING | REVIEW | Needs Review | |
| 02/05/2008 | WILLDAN | ADA | REVIEW | Needs Review | |
| 02/05/2008 | WILDAN | 2ND PARTY REVIEW | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/05/2008 | SUE REEVES | OUT TO CUSTOMER | Completed |