Permit Number: T07CM04780
Parcel: 12009308A

Address:
4823 S 6TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04780
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2008 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T07CM04780
4823 S. 6th Ave
ADA changes and firewall installation

TRANSMITTAL DATE: 1-17-08

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The minimum width of a sidewalk is four (4) feet per DS 2-08.5.1.A. Key note #1 indicates 36". Revise note and add dimension to meet code.

2. Per DS 2-08.4.1 all sidewalks shall be physically separated from any vehicular use area (front of the parking spaces) by means of curbing, grade separation, barriers, railings or other means.

If grade separation is used for the sidewalk a handicap ramp will be required immediately north of the landing in front of the handicap parking access aisle.

3. Per ANSI 117.1-2003 Sec. 502.5 the maximum slope within a handicap access aisle is 1:48. Key note #6 indicates the slope not to exceed 1:20. Revise.

4. Provide a detail of the required handicap parking signage, clearly indicating size, verbiage and height above grade. (min. height above grade to the bottom of the main sign is seven (7) feet).

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T07CM04780.doc
01/17/2008 WILDAN 2ND PARTY REVIEW REVIEW Denied January 15, 2008

City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Tucson Rodeo Museum ADA – 1ST REVIEW
CITY OF TUCSON LOG NO. T07CM04780
WILLDAN PROJECT NO. 13881-7085

The initial review for the above project has been completed. This letter contains comments, which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all indicated corrections and revisions to the plans must be made, and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2006 IBC, 2006 IMC, 2006 IECC, 2006 UPC, 2006 IFC, and the 2005 NEC (with local modifications). Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Roger Brooks.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
A-3 Existing IIB 7,942


ARCHITECTURAL / ACCESSIBILITY COMMENTS:
Sheet A 1.2
Please note on the plans how the gap between the two structures will be sealed.

Please note on the plans the status of the south wall of the adobe structure. It appears that it has been demolished.

STRUCTURAL COMMENTS:
Sheet A 1.2
Please note on the plans the reason for the construction of the firewall. Occupancy Separation? Over-Area requirement?

Please show the structural engineering on the firewall, including the roof supports/attachments and structural notes.

It appears that the 12” X 12” footing for the firewall is insufficient to support the 22-foot wall, please clarify with structural engineering to support the design.

Please show the framing details on the plans and the plan detail.

PLUMBING COMMENTS:
Not part of this review.

MECHANICAL COMMENTS:
Not part of this review.

ELECTRICAL COMMENTS:
Not part of this review.

ENERGY CODE COMMENTS:
Not part of this review.



Sincerely,

WILLDAN



Roger A. Brooks, C.B.O., V.P.
Division Manager

RAB/jk/cc
01/17/2008 WILLDAN ADA REVIEW Denied SEE 2ND PARTY COMMENTS
01/22/2008 BIANCA RAMIREZ ENGINEERING REVIEW Needs Review
01/22/2008 ROBERT SHERRY WATER REVIEW Approved
12/24/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed