Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04780
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/20/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide CW shut off valves for each building entrance. Reference Section 605.2, UPC 2006. 2. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference Section 609.10, UPC 2006. 3. Include all fixtures when calculating the total demand and determining pipe sizes (i.e. correct the arithmetic in the calculations). Reference Section 610.1, UPC 2006. 4. Calculate the water demand using the fixture units shown in Tables 6-5 or A-2 (assembly). Reference Section 610.3, UPC 2006. 5. Verify the size of the pipe serving the flush valves. Reference Sections A5.1 and A6.1, UPC 2006. 6. Provide the rim elevation of the sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson. 7. Show the size, material, and slope of the building sewer (sheet G0.2). Reference Sections 103.2.3 and 718.1, UPC 2006. 8. Provide cleanouts in the building sewer at intervals not exceeding 100 feet and show how they are to be installed. Reference Sections 719.1 and 719.5, UPC 2006 |
| 12/20/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Reprint M1.1 so that the background is legible. Reference Section 106.3.1, IMC 2006. |
| 12/20/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/21/2007 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 12/21/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/21/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04780 12/21/07 1. Provide electrical power for EF-3. Reference Sheet M1.1. 2. Provide electrical power for WH-1 and WH-2. Reference Sheet P2.1. 3. Short circuit calculation, with a utility available fault current of 22,000A for this 400A commercial single-phase service, is based upon an underground secondary of at least 45' in length. The underground secondary on the plans scales out to be about 15'. 4. Short circuit calculation uses a 145' utility secondary length. The underground secondary on the plans scales out to be about 15'. |
| 12/21/2007 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review | |
| 12/21/2007 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/21/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/21/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |