| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/13/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 02/15/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide a letter from Tucson Water confirming that the use of a 2" water meter will be allowed for this project (230 fixture units on a flush valve system equates to a demand of 97 GPM which exceeds the 80 GPM maximum set by Tucson Water for 2" meters.) |
| 02/20/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/21/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/29/2008 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |