Permit Number: T07CM04766
Parcel: 12306105A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM04766
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 1/25/08
Activity: T07CM04766
Address: 2131 E. Drachman St.
Applicant: Bob Lanning

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

STRUCTURAL:
3. Include wall loads in load calculation for lintel design.
4. Footing design specifies 3' square footing under columns. Provide footing detail that reflects design criteria.
5. Provide consistent information between plan view and section view for footing details.

PLUMBING PLAN:
6. Provide the maximum developed length of water line from the meter the furthest appliance served, and the diameter of the water line, UPC Table 6-6.
7. The Tucson Water policy adopted 3/2/07 limits the maximum demand for a 5/8" water meter (there are no ¾" meters for Tucson Water service) to 10GPM, confirm with Tucson Water that the existing meter will be able to meet the new water demand.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review
12/28/2007 GERRY KOZIOL WWM REVIEW Denied needs 8th floor credit WWM evaluation

Final Status

Task End Date Reviewer's Name Type of Review Description
01/30/2008 CPIERCE1 OUT TO CUSTOMER Completed