Permit Number: T07CM04762
Parcel: 30503026B

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM04762
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2007 DAVE MANN FIRE REVIEW Approved
12/20/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/24/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 6 OF 19: CLARIFY DISINFECTION BUILDING AND SECONDARY CONTAINMENT. ITEMS SHOWN IN CALCULATIONS ARE NOT SHOWN ON PLAN OR SECTION. OR ARE BUILDING, SUPPORT BEAMS, AND CONTAINMENT ALL PREMANUFACTURED?
2. SHEET 9 OF 19: SECTION CUT ON 'MOUNTING FRAME ELEVATION' SHOULD BE DENOTED 'E' RATHER THAN 'D'.
3. SHEET 9: NOTE 7 UNDER 'EQUIPMENT': CALCULATIONS DENOTE #10 TEK SCREWS RATHER THAN #7 SHEET METAL SCREWS INDICATED ON SECTION. PLEASE CLARIFY.
4. SHEET 9: NOTE BRACE SIZE ON DRAWING SECTION PER CALCULATIONS.
5. SHEET 9: REMOVE INDICATED REINFORCEMENT IN POST FOUNDATION PER CALCULATIONS.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/31/2007 CPIERCE1 OUT TO CUSTOMER Completed
12/31/2007 SUE REEVES REJECT SHELF Needs Review