| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/20/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/20/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/24/2007 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET 6 OF 19: CLARIFY DISINFECTION BUILDING AND SECONDARY CONTAINMENT. ITEMS SHOWN IN CALCULATIONS ARE NOT SHOWN ON PLAN OR SECTION. OR ARE BUILDING, SUPPORT BEAMS, AND CONTAINMENT ALL PREMANUFACTURED? 2. SHEET 9 OF 19: SECTION CUT ON 'MOUNTING FRAME ELEVATION' SHOULD BE DENOTED 'E' RATHER THAN 'D'. 3. SHEET 9: NOTE 7 UNDER 'EQUIPMENT': CALCULATIONS DENOTE #10 TEK SCREWS RATHER THAN #7 SHEET METAL SCREWS INDICATED ON SECTION. PLEASE CLARIFY. 4. SHEET 9: NOTE BRACE SIZE ON DRAWING SECTION PER CALCULATIONS. 5. SHEET 9: REMOVE INDICATED REINFORCEMENT IN POST FOUNDATION PER CALCULATIONS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/31/2007 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 12/31/2007 | SUE REEVES | REJECT SHELF | Needs Review |