Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04761
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/19/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/19/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the termination of the OA and EA ducts. 2. Show how the fan coil is to be mounted to the structure. 3. Clarify the supply and return ducting for the fan coil. 4. Clarify how the condensate piping is to terminate - air gap or air break? 5. Clarify the location of the heat pump - how far is it from other equipment. |
| 12/19/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/19/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/19/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/19/2007 | RSHERRY1 | WWM | REVIEW | Passed | No additional plumbing fixtures |
| 12/19/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/19/2007 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 12/19/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/19/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |