Permit Number: T07CM04761
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04761
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2007 STEVE SHIELDS ZONING REVIEW Approved
12/19/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the termination of the OA and EA ducts.
2. Show how the fan coil is to be mounted to the structure.
3. Clarify the supply and return ducting for the fan coil.
4. Clarify how the condensate piping is to terminate - air gap or air break?
5. Clarify the location of the heat pump - how far is it from other equipment.
12/19/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/19/2007 ROBERT SHERRY WATER REVIEW Approved
12/19/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/19/2007 RSHERRY1 WWM REVIEW Passed No additional plumbing fixtures
12/19/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/19/2007 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/19/2007 DAVE MANN FIRE REVIEW Approved
12/19/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed