Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04760
Parcel: 128100810

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM04760
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04760 3/11/08

1. Add existing sign circuit to load calculations.
2. Add Smoke Detector to load calculations.
3. Account for Track Lighting load at 75 VA/LF. Reference NEC 220.43 (B).

Final Status

Task End Date Reviewer's Name Type of Review Description
03/12/2008 CINDY AGUILAR APPROVAL SHELF Completed
03/12/2008 CINDY AGUILAR OUT TO CUSTOMER Completed