Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04760
Parcel: 128100810

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM04760
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/26/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. I believe that the section of CW pipe between the mop sink and the first hand sink should be 1", not ¾". (I have included the water supply to the oven as 1 fixture unit.) In addition, the HW and CW drops to the hand sinks would be counted as 1.5 fixture units (3/4 of the total fixture units for the fixture; see footnote 3, Table 6-5, UPC 2006). [The submitted water pressure calculations do not support the size of water piping to the fixtures. Reference Section 610.1, UPC 2006.]
2. Clarify the location of the vented flow control device provided for the hydromechanical grease interceptor. Per Section 1014.2.1, UPC 2006 it shall be readily accessible and per the manufacturer's instructions, it should be as close as possible to the underside of the fixture. Reference Section 310.4, UPC 2006.
02/26/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved