Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2008 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PREVIOUS CORRECTION NOTE 1B. SHOW ALL ACCESSIBLE ROUTE ELEVATION SLOPES; RESPONSE ACCEPTED. PLEASE BE AWARE THAT WE ARE CONSIDERING A POLICY CHANGE ASKING FOR SPOT ELEVATIONS ON ACCESSIBLE ROUTES.

2) PREVIOUS CORRECTION 2. PROVIDE EM EGRESS LIGHTING WITH BATTERY BACK UP IBC 1006.3. YOU HAVE CREATED 2 REQUIRED EXITS BY CREATING 2 SEPARATE ACCESSIBLE EGRESS ROUTES.

3) IBC SECTION 2902.4 DOES NOT ALLOW THE REAR ACCESSIBLE ROUTE TO THE RESTROOM TO GO THROUGH STORAGE.
02/06/2008 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review
02/06/2008 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review