Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04760
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/29/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. ROUTING TOILET ACCESS OUT THE FRONT DOOR, AROUND THE STRIP CENTER, THROUGH THE BREEZE AND ENTRANCE THROUGH THE BACK DOOR REQUIRES SEVERAL OTER REQUIREMENTS, IBC 1109.2, ANSI 117.1-402.2, : 1A. SUBMIT SITE PLAN IDENTIFYING EXACT ACCESSIBLE ROUT. 1B. SHOW ALL ACCESSIBLE ROUTE ELEVATION SLOPES 1C. VERIFY REAR DOOR IS ACCESSIBLE; ELEVATION, LANDINGS, DOOR AND HARDWARE, IBC SECTION 1105.1 1D. PROVIDE ADDITIONAL COSTS TO MAKE THIS ROUTE 100% ACCESSIBLE 2. PROVIDE EM EGRESS LIGHTING WITH BATTERY BACK UP IBC 1006.3 3. PROVIDE APPROVED APPEAL FROM BUILDING OFFICIAL FOR BOTTLELESS WATER COOLER |
| 02/05/2008 | GBONILL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 02/05/2008 | GBONILL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |