Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04760
Parcel: 128100810

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04760
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the outside air supply to the building as required to comply with footnote f, Table 403.3, IMC, IMC 2006.
01/11/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for mercantile occupancy.
2. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 504.4, IECC 2006.
3. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 btu per inch/h °F on the first 8 feet of supply and discharge piping. Reference Section 504.5, IECC 2006.
4. The submitted water pressure calculations do not support the size of water piping to the fixtures. Reference Section 610.1, UPC 2006.
5. Resize the drainage piping to conform to Table 7-5, UPC 2003, with no more than 8-drainage fixture units on a 2" horizontal waste line. Reference Section 703.2, UPC 2006
6. Provide a floor drain in the kitchen. Reference Sections 411.2.2 and 704.3, UPC 2006.
7. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference Sections 304.0 and 801.2.3, UPC 2006.
8. Modify trap arm length for the floor sink by the walk-ins to conform to Table 10-1, UPC 2006. Reference Section 1002.2, UPC 2006.
9. Provide a vent to protect the grease trap from siphonage and backpressure. Reference Sections 1002.1 and 1014.2.3, UPC 2006.
10. Based on the manufacturer's recommended sizing procedure, the specified hydromechanical grease interceptor is too small; revise accordingly. Reference Sections 310.4 and 1014.2.2, UPC 2006.
11. Provide a vented flow control device for the hydromechanical grease interceptor per Section 1014.2.1, UPC 2006 and per the manufacturer's instructions. Reference Section 310.4, UPC 2006.
01/17/2008 SREEVES1 WWM REVIEW Approved
12/20/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/27/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. CHANGE ALL "A2" OCCUPANCY REFERENCES TO "M" AND CHANGE ALL S.F. SIZE REFERENCES TO 1,318 S.F. GROSS
2. AT DETAILS A1, A2, AND A3/A-6.1: DO NOT BRACE INTERIOR PARTITIONS TO WEB MEMBER OF TRUSSES
3. PROVIDE HI/LOW EWC AS PER IBC TABLE 2902.1 AND ANSI 117.1, 602.4
4. $17,000.00 EVALUATION APPEARS TO BE TOO LOW, JUSTIFY.
5. ACCESSIBLE ROUTE TO TOILET MAY NOT BE THROUGH A KITCHEN NOR A STORAGE ROOM; IBC 2006 SECTION 2902.4

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
01/25/2008 SHANAE POWELL REJECT SHELF Completed