Permit Number: T07CM04744
Parcel: 13734001E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04744
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review Impact Fee's Do Apply; West District; 1,142 Square Feet; Permit Issued Before 1/16/2008 $2,230.30; Permit Issued on and After 1/16/08 $4,590.59
01/11/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. The 2006 IPC may be used under an appeal to the building official.
01/11/2008 ROBERT SHERRY WATER REVIEW Approved
01/14/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The 2006 International Mechanical Code with Local Amendments is the relevant code for this project.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
3. Complete recirculation of ventilation air from toilet rooms is prohibited; controlling the exhaust fans with the restroom lights will result in recirculation of the air from the restroom. Reference Section 403.2.1 (3), IMC 2006.
4. Provide calculations demonstrating adequate ventilation. Reference Section 403, IMC 2006.
5. Clarify how the "preforated" stainless steel panel located behind the hood complies with the requirements of Section 507.9, IMC 2006. Note that a smooth, non-absorbent, cleanable, and non-combustible surface shall extend 18" in all directions beyond the hood.
6. Show that make up air or HVAC ducts connected to or within 18" of a Type I hood comply with the requirements of Section 506.3.1.2, IMC 2006.
7. Provide information to show that the operation of the Type I hood and the hood exhaust fan, EF-1, complies with Section 507.2.1.1, IMC 2006.
12/19/2007 GERRY KOZIOL WWM REVIEW Approved
12/20/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/28/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. CITY OF TUCSON REQUIRES ALL PLANS AND DOCUMENTS USE PRINTING THAT IS A MINIMUM OF 1/8" WITH ALL CAPITAL LETTERS TO FACILITATE MICROFILMING OF DOCUMENTS FOR PERMANENT RECORDS.
2. ALL CODE REFERENCES SHOULD BE TO 2006 IBC. VERIFY THAT ALL PLANS MEET 2006 REQUIREMENTS.
3. ADA IS A FEDERAL ACT, NOT A BUILDING CODE. INSERT REFERENCE TO ANSI 117.1-2003.
4. OCCUPANCY CLASSIFICATION IS A2 ONLY. REMOVE M.
5. VERIFY BOTTOM OF HANDICAP PARKING SIGN TO BE 84".
6. CLARIFY HANDICAP ACCESS ROUTES FROM STREET AND FROM PARKING SPACES, INCLUDING ROUTE SLOPES.
7. HIGH/LOW DRINKING FOUNTAIN REQUIRED.
8. TOILET PAPER DISPENSER SHOULD BE LOCATED 7" TO 9" IN FRONT OF WATER CLOSET. VERIFY HEIGHT.
9. VERIFY THAT STRUCTURAL CALCULATIONS MEET 2006 IBC CODE REQUIREMENTS. REFERENCE THAT CODE.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/01/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
02/01/2008 SHANAE POWELL REJECT SHELF Completed