Permit Number: T07CM04722
Parcel: 11706187D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04722
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/26/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
02/26/2008 DROBEY1 WWM REVIEW Needs Review
02/26/2008 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
02/26/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/17/2007 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/18/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a double check valve (ASSE Std. 1015) for the ice machine.
2. Provide a reduced pressure backflow preventer ( ASSE Std. 1013) for the espresso machine.
3. Provide a vent for the hand sink
4. Provide an indirect waste receptor for the espresso machine.
12/18/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/18/2007 MARTIN BROWN FIRE REVIEW Approved
12/18/2007 ROBERT SHERRY WATER REVIEW Approved
12/18/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2008 DELMA ROBEY OUT TO CUSTOMER Completed