Permit Number: T07CM04700
Parcel: 12008604C

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM04700
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2007 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/14/2007 STEVE SHIELDS ZONING REVIEW Approved
12/18/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/18/2007 MARTIN BROWN FIRE REVIEW Approved
12/19/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/19/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/19/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM04700 12/18/07

1. Circuiting of emergency lighting is in violation of NEC 700.12 (F).
2. Mechanical schedule specifies that Exhaust Fans take 115V power, but they are powered on 240V. Please clarify.
3. Address Fan Units 3 and 4.