Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM04700
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/14/2007 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 12/14/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/18/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/18/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/19/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/19/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/19/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07CM04700 12/18/07 1. Circuiting of emergency lighting is in violation of NEC 700.12 (F). 2. Mechanical schedule specifies that Exhaust Fans take 115V power, but they are powered on 240V. Please clarify. 3. Address Fan Units 3 and 4. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/19/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 12/19/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 12/19/2007 | DELMA ROBEY | REJECT SHELF | Completed |