Permit Number: T07CM04696
Parcel: 12419037A

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T07CM04696
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Clean Energy
T07CM04696
Site Plan (3rd Review)

TRANSMITTAL DATE: August 25, 2008

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance.

2. Engineering has required that a DEVELOPMENT STANDARDS MODIFICATION REQUEST (DSMR) be approved prior to approval of the site plan. Zoning cannot approve the site plan until the DSMR has been approved. Provide the DSMR number, date of approval and any conditions of approval on the site plan.

3. Once the above comments have been approved Zoning is willing to provide an over-the-counter review. Call or email to schedule an appointment for this review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t07cm04696-3rd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
09/02/2008 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. One canopy tree must be provided for every thirty-three (33) linear feet of the street landscape borders. Re-locate and add trees as necessary.

2. Fifty (50) percent or more of the street landscape border area must have shrubs and vegetative ground cover per LUC 3.7.2.4. The screening is requirement is in addition to the landscape coverage requirement; Encelia farinose will cover approximately 3.5 sq. ft. for each individual plant additional vegetative material is necessary to meet coverage.

3. Indicate square footage of all landscaped areas and calculation of the percentage of vegetative coverage per DS 2-07.2.2.2.g.

4. Include with re-submittal DDO approval documentation. Indicate on the lower right hand corner of the site plan, the case number, date of approval, and any conditions imposed.

5. If clarification is needed for above comments call 520-837-4950 or email Andrew.Connor@tucsonaz.gov

6. Additional comments may apply.
09/15/2008 JASON GREEN ENGINEERING REVIEW Approv-Cond DATE: September 15, 2008
SUBJECT: 1755 E Winsett St Site Plan- 3rd Engineering Review
TO: General Physics Corporation
LOCATION: T14S R14E Sec18 Ward 5
REVIEWERS: Jason Green, CFM
ACTIVITY: T07CM04696 (Site Plan)


SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised site plan (T07CM04696) for the above referenced property. Engineering Division recommends conditional approval of the site plan application at this time. The following items need to be addressed prior to the site plan being stamped approved:


SITE PLAN COMMENTS:

1) DS Sec2-02.2.1.A.12: It is acknowledged that a DSMR (DS08-41) has been approved (22AUG08) for this project for modifying the Development Standards Sec.3-01.3.3.4 and Sec.6-01.3.2.A. Provide a General Note to list the DSMR number, the Development Standards being modified along with the date of DSMR approval.

2) Provide the Geotechnical Evaluation (ConformaTECH, 11DEC07) that was submitted on the 1st review, this was not included in the 2nd nor 3rd submittal and is required for record keeping purposes

3) Review and approval from TDOT Permits and Codes for all improvements within the public right-of-way will be required. A right-of-way use permit application will be required prior to construction. Refer to the following links for TDOT Forms and applications:

a) http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/applications.html /

b) http://www.dot.ci.tucson.az.us/engineering/pia.php

c) Or contact Thad Harvison at 837-6592 for all additional questions regarding r-o-w.

4) Be advised that further comments may be forth coming on resubmittal of the site plan.


GENERAL COMMENTS:

Please provide the revised Site Plan with the listed DSMR and the required Geotechnical Evaluation (ConformaTECH, 11DEC07). Once all items have been addressed the Site Plan will be stamped approved by the Engineering Division.

If you have any questions or to schedule an appointment I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2008 CPIERCE1 OUT TO CUSTOMER Completed
09/25/2008 SUE REEVES REJECT SHELF Completed