Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04696
Parcel: 12419037A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T07CM04696
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE TRUNCATED DOMES AT BOTTOM OF ALL ACCESSIBLE RAMP, ANSI 406
2. CLARIFY ACCESSIBLE ROUTE IBC 1104
3. CLARIFY THAT SLOPES OF ACCESSIBLE ROUTE ANSI 402
4. PROVIDE STRUCTURAL CALCULATIONS FOR LIGHT POLE FOUNDATION
03/19/2008 MARTIN BROWN FIRE REVIEW Denied Please clarify location of Emergency Shut Off location(s).
Also, be advised that a separate permit for the storage tank will be required through the Fire Department. Please provide all relevant cut sheets, listings, piping plans, etc.
03/24/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the required dimensions for the overflow scuppers for the canopy. Reference: Section 1101.11, UPC 2006.
2. Indicate that all hoses, hose connections, dispensers, and gas detection systems shall be listed, and that vehicle fueling connections shall be listed and labeled. Reference: Section 413.2.2, IFGC 2006.
3. Show the location of the remote manual shutoff valves and th4e emergency shutdown controls for the dispensers and for the compressors. Reference: Section 413.8, IFGC 2006.
4. Show the locations and termination design of the vent stacks noted on sheet M02. Reference: Section 106.3.1, IFGC 2006.
03/24/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/24/2008 ROBERT SHERRY WATER REVIEW Passed
03/26/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/08/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Clean Energy
T07CM04696
Building Plan (1st Review)

TRANSMITTAL DATE: April 8, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t07cm04696.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
04/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Fixture S1 is listed as 100W MH on the lighting code compliance luminaire schedule, but a note on the same page, E04 has it as 250W HPS. Please clarify, and note any changes as necessary to the lighting compliance calculations. Note that Detail 6 Sheet E06 #3 states "175W METAL HALIDE,208V 150W HPS 120-277 VAC"
2. Please note that the area for application of the Tucson Lighting Code is 0.362 acre, not 0.394, for a total of 108,609 allowed FCO lumens, not 118,275.
3. Registered Structural Engineer shall provide calculations and detail for lighting pole and foundation. Please coordinate this with other disciplines.
4. Labeling at Single Line Diagram indicates that fuses protect the loads, but the symbol used more closely resembles that of a circuit breaker. Please clarify, and revisit Ground Fault and Short Circuit Protection for the ½ HP motors and 5 HP Air Compressor.
5. Clarify the load on the secondary of XFMR T2.
6. Please specify the Main Bonding Jumper size at the service disconnect as 400 MCM. Reference NEC 250.28 (D).
7. Gas Dryer is specified at 100A on Sheet M01. Electrical calls for a 22A Dryer on the line diagram. Please clarify.
8. Provide dimensions on area classification at skid.
9. Specify the exact conduit type intended for that which is run underground below classified locations. Reference NEC 514.8.
10. In the notes pertaining to Sealing and Drainage on Sheet E01, please specify that listed seals be provided in each dispenser conduit run. Reference NEC 514.9 (A).
11. Provide for means to disconnect dispenser grounded conductors simultaneously with the phase conductors. Reference NEC 514.11 (A).
12. Add the E-STOPS to the dispensers and exterior skid wall on the Power Plan Sheet E05, which are indicated on Sheet M04, E-STOPS, Fire Extinguisher, & Signage Plan. Reference NEC 514.11 (C).
13. Provide the means to remove all external voltage sources, including feedback, during maintenance. NEC 514.13.
14. Provide detailed specifications for any circuit breakers and motor controllers in the Class I Division 2 area. Reference NEC 501.115 (B).
15. Demonstrate compliance with NEC 501.125 (B). Suggest cut sheets of equipment.
16. Note 2 on Sheet E05 refers to Sheet E09 for location of conduit stubouts. This is not clear on Sheet E09.
17. Note 12 on Sheet E01 specifies an elevation for pole bases with respect to the 100 year flood level. If flood plain issues are a concern, provide drawings which call out these levels, and consider the effects of such levels on such equipment as the electrical service, the switchboard, and the skid equipment.
18. Add the following note to the lighting plans: "Special Inspection required per Tucson Lighting Code Section 16."
Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008)
04/08/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Clean Energy
T07CM04696
Building Plan (1st Review)

TRANSMITTAL DATE: April 8, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t07cm04696.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
04/16/2008 GERRY KOZIOL WWM REVIEW Passed
04/25/2008 JASON GREEN ENGINEERING REVIEW Denied Building Plans can not be approved prior to site plan approval. Resubmit the building plans with a stamped approved site plan for review. JG

Final Status

Task End Date Reviewer's Name Type of Review Description
05/02/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
05/02/2008 SHANAE POWELL REJECT SHELF Completed