Permit Number: T07CM04673
Parcel: 11603197B

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T07CM04673
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2008 DAVE MANN FIRE REVIEW Approved
05/23/2008 RONALD BROWN ZONING HC SITE REVIEW Denied 1. RELOCATE ACCESSIBLE PARKING SIGNAGE TO LINE OF CONCRETE HEADER. REVERENCE DETAIL 1/2.
2. RAISE HEADER 6" AFG AT AREAS NOT ACCESSED FROM PARKING AISLES.
3. SEE SUGGESTED REVISED DESIGN PROPOSAL FOR STACKED ACCESSIBLE PARKING ON ONE OF NOTED PLAN SETS.
05/27/2008 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Existing vehicle use area on the site is subject to the zoning regulations in effect at the time the existing development received approval LUC 3.7.1.2. Parking lot configuration has changed from previously approved plans; Verify the existing VUA meets minimum landscape requirements at the time of last plan approval. Indicate if required trees are to be removed and replaced if necessary. Include the location, size, and name of existing vegetation to remain in place.

2. Include with re-submittal approval documentation for use of 5' wall. Indicate on the lower right hand corner of the site plan, the variance case number or Docket and Page of recorded joint use agreement, date of approval, and any conditions imposed.
05/27/2008 ANDREW CONNOR NPPO REVIEW Approved
06/06/2008 HEATHER THRALL ZONING REVIEW Approved
06/18/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the size of the water meter
b. the location and size of the public sanitary sewer and
c. the location, invert, and rim elevation of the manholes.
Reference: City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006
06/23/2008 JASON GREEN ENGINEERING REVIEW Approv-Cond DATE: June 23, 2008
SUBJECT: 1300 N Greasewood Road Site Plan- 3rd Engineering Review
TO: Grenier Engineering, ATTN: Kent Delph, P.E.
LOCATION: T14S R13E Sec04 Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: T07CM04673 (Site Plan)

SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised site plan (T07CM04673), Drainage Report (Grenier Engineering, Inc., 10DEC07 revised 18MAR08, 15MAY08) and Geotechnical Evaluation (Western Technology Inc., 27JUL07 Addendum 25FEB08) for the above referenced property. Engineering Division recommends conditional approval of the site plan at this time. The following item must be addressed prior to installation of the landscaping:

" Revise the landscape plan to show that the required basin maintenance access ramp is unobstructed by the planting of required trees/shrubs. The landscape plan submitted shows the placement of 2 trees/shrubs within the limits of the 15-foot ramp, revise.


If you have any questions I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
06/23/2008 VFLORES1 OUT TO CUSTOMER Completed