Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE ALL
Permit Number - T07CM04673
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/21/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
05/23/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Denied | 1. RELOCATE ACCESSIBLE PARKING SIGNAGE TO LINE OF CONCRETE HEADER. REVERENCE DETAIL 1/2. 2. RAISE HEADER 6" AFG AT AREAS NOT ACCESSED FROM PARKING AISLES. 3. SEE SUGGESTED REVISED DESIGN PROPOSAL FOR STACKED ACCESSIBLE PARKING ON ONE OF NOTED PLAN SETS. |
05/27/2008 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. Existing vehicle use area on the site is subject to the zoning regulations in effect at the time the existing development received approval LUC 3.7.1.2. Parking lot configuration has changed from previously approved plans; Verify the existing VUA meets minimum landscape requirements at the time of last plan approval. Indicate if required trees are to be removed and replaced if necessary. Include the location, size, and name of existing vegetation to remain in place. 2. Include with re-submittal approval documentation for use of 5' wall. Indicate on the lower right hand corner of the site plan, the variance case number or Docket and Page of recorded joint use agreement, date of approval, and any conditions imposed. |
05/27/2008 | ANDREW CONNOR | NPPO | REVIEW | Approved | |
06/06/2008 | HEATHER THRALL | ZONING | REVIEW | Approved | |
06/18/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the site drawing to include the following information: a. the size of the water meter b. the location and size of the public sanitary sewer and c. the location, invert, and rim elevation of the manholes. Reference: City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006 |
06/23/2008 | JASON GREEN | ENGINEERING | REVIEW | Approv-Cond | DATE: June 23, 2008 SUBJECT: 1300 N Greasewood Road Site Plan- 3rd Engineering Review TO: Grenier Engineering, ATTN: Kent Delph, P.E. LOCATION: T14S R13E Sec04 Ward 1 REVIEWERS: Jason Green, CFM ACTIVITY: T07CM04673 (Site Plan) SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised site plan (T07CM04673), Drainage Report (Grenier Engineering, Inc., 10DEC07 revised 18MAR08, 15MAY08) and Geotechnical Evaluation (Western Technology Inc., 27JUL07 Addendum 25FEB08) for the above referenced property. Engineering Division recommends conditional approval of the site plan at this time. The following item must be addressed prior to installation of the landscaping: " Revise the landscape plan to show that the required basin maintenance access ramp is unobstructed by the planting of required trees/shrubs. The landscape plan submitted shows the placement of 2 trees/shrubs within the limits of the 15-foot ramp, revise. If you have any questions I can be reached at 837-4929. Jason Green, CFM Senior Engineer Associate Engineering Division COT Development Services |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/23/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |