Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04653
Parcel: 138090840

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM04653
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: T07CM04653
Activity: 2/07/08
Address: 291 W. Calle Nido De Amor
Applicant: Nora Durazo

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

FLOOR PLANS:
2. Indicate on the floor plan the intended use of the proposed room.
3. Specify the size and type of all windows and doors along with their U-value and solar heat gain coefficient, N1102.1

FOUNDATION PLANS:
4. All exterior framed walls require continuous concrete footings min. 12"wide x 12" below grade with treated sill plates and anchor bolts per R319.1 & R403.1.6 (including carport and porch enclosures).

STRUCTURAL PLANS:
5. Indicate the spacing of the existing 2x10 rafters.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/15/2008 CPIERCE1 OUT TO CUSTOMER Completed