Permit Number: T07CM04645
Parcel: 118220550

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM04645
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2008 MICHAEL ST. PAUL ZONING REVIEW Denied This is a multi-family site in the R-3 zone. A commercial site plan is required. Please see Development Standard 2-02 for the basic requirements of a site plan.
01/08/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity: T07CM04645
Date: 1/09/08

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

I. GENERAL REQUIREMENTS:
" Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
" As of June 13, 2007 the City of Tucson has adopted the 2006 IRC with the exception of the plumbing portion which has been replaced with the 2006 UPC with amendments. The plans should reference these codes, or appeal to the Building Official for 2000 or 2003 IRC, and 1994 UPC-design approvals.

II. FOUNDATION PLANS:
" Provide a note for termite treatment, R320 as amended.

III. STRUCTURAL PLANS:
" Truss calculations must be signed, dated and wet-sealed by an engineer who is registered in Arizona. Truss calculations shall be cross-referenced to the floor plans. Note the requirement for a deferred submittal if the truss calculations will not be submitted with the plan review.

IV. SECTIONS - DETAILS:
" Specify ceiling covering. Note: Ceiling gypsum board must be either 5/8" or ½" sag resistant when applied to ceilings framed at 24" o/c, IRC table R702.3.5 footnote d.
" Specify roof sheathing material, 803.1.

V. PLUMBING PLAN:
" Provide an individual water meter for residence, P2602.1.1.
" Provide a reasonable figure for the maximum developed length from the water meter the furthest fixture served.
" Specify the size of the water meter and the available pressure for the property.
" Provide accurate fixture unit values, UPC Tables 6-5 and 7-3.

VI. MECHANICAL PLAN:
" Specify a mechanical system with a minimum SEER rating of 13, DOE 10-430.
" Show supply and return ducts with minimum R-8 insulation, R1103.2.1.

VII. ELECTRICAL PLAN:
" Bedroom outlets shall be arc-fault protected (receptacles, lights, and smoke detectors) by combination arc-fault devices, E3802.12.
" Provide 5000 VA for the electric clothes dryer (taken at 100%) in the electrical load calculations, Table E3604.2(1).
" Specify the grounding electrode method and the size of the grounding electrode conductor, E3503.4, E3508.1.
" Specify the diameter of the service conduit, TEP SR-305.
" Show receptacle outlets at wall spaces 2' or more, E3801.2.

VIII. OUTDOOR LIGHTING CODE
" Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.
" Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).

If you have any questions please contact:
Clayton Trevillyan
(520) 837-4913
City of Tucson Residential Plan Review
12/20/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/22/2008 SUE REEVES OUT TO CUSTOMER Completed
01/22/2008 SHANAE POWELL REJECT SHELF Completed