Permit Number: T07CM04641
Parcel: 135103980

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM04641
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2008 GERRY KOZIOL WWM REVIEW Approved
02/07/2008 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T07CM04641

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets (clouded revision notation is not necessary for comment changes).

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

Construction drawing guidelines are available from the residential desk of the Development Services Division.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

" Show the code used for construction: 2006 International Residential Code.
" Show the scale on each drawings (¼" = 1'), R106.1.1.
" Provide legible notation: minimum 1/8" lettering (sheet A-6).
" Interior alterations require the installation of smoke alarms at existing bedrooms, R313.2.1.

SITE PLAN:

1. Indicate the location of buildings, utility meters and service lines from property line to building, R106.1.1.
2. Specify overhead or underground electrical service, UAC amendment section 108.

FLOOR PLANS:

1. Clarify if the Laundry Room is a conditioned space, R106.1.1.
2. Remove electrical circuits and devices from sheet A-1. This is not consistent with sheet E-4.

SECTIONS - DETAILS:

1. Show wood framing members resting on concrete as pressure treated, R319.1 item 2
2. Note and specify the size, spacing and length of sill plate anchors, R403.1.6.
3. Show new ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.
4. Specify #15 water-resistive barrier over studs of all new exterior walls, R703.2.
5. Clarify the term "sr" as gypsum board.

MECHANICAL PLANS:

1. Show any existing supply registers or heating/cooling appliances, M1302.1.
2. Show dryer vent size and location for venting to exterior, M1501.

ELECTRICAL PLANS:

1. Provide a panel schedule showing descriptions consistent with the electrical plan, sheet E-4 circuit #25, 26 & 27, E3304.11 & E3606.2.
2. Designate the circuit number at the location of each light fixture, receptacle, appliance and equipment disconnect switch (include the microwave), E3603.5. Mark existing outlets, shown for reference only, as "E".
3. Weatherproof covers are required for preventing moisture from entering electrical boxes in damp or wet locations, E3805.11.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Show the "R" values of insulation for new conditioned spaces on the plans. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13, N1101.2.
2. Both standard and high density R-30 batt insulation requires a space greater than provided with 2" x 8" framing. Identify the product that provides the intended value.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review