Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 3950 N Sun Tran Blvd, Bus Wash
T07CM04640

The Electrical Plans have been denied for the following:

1.The 2005 NEC 230.2 allows only one service to supply a building,
2. There are two sets of plans submitted, the existing set approved originally for the project, which shows an existing SES service section rated at 1200 amps, 277/480 volts that provides two 250 amp panels for future use of Water Reclaim Systems, located in the Electrical Rm ,#104.
The new plans submitted for the Bus Wash include a new 200 amp 277/480 volt service notated on sheet RE-2, at the front of the building, then sheet RE-3 shows a 400 amp 277/480 volt one line diagram of the service .
The power should be obtained through the power provided.

Provide response to each question and state why the drawings were submitted in this manner.


Ray T Majuta
Elect Plan Ck,
PDSD, City of Tucson
10/05/09