Permit Number: T07CM04634
Parcel: 128100530

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04634
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2007 TERRY STEVENS ZONING REVIEW Approved
12/12/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/12/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04634 12/12/07

1. Provide electrical power for the water heater. Please note that the water heater is specified for 230V, so verify with Plumbing that this is OK to run on 208.
2. Panel L2B-3 is 225A on Line Diagram, but 200A on panel schedule. Please clarify.
12/12/2007 ROBERT SHERRY WATER REVIEW Approved
12/12/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/12/2007 PAUL MACHADO ENGINEERING REVIEW Approved
12/12/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/12/2007 DAVE MANN FIRE REVIEW Approved
12/12/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/13/2007 GERRY KOZIOL WWM REVIEW Approved