Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04634
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/12/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
12/12/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
12/12/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04634 12/12/07 1. Provide electrical power for the water heater. Please note that the water heater is specified for 230V, so verify with Plumbing that this is OK to run on 208. 2. Panel L2B-3 is 225A on Line Diagram, but 200A on panel schedule. Please clarify. |
12/12/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/12/2007 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/12/2007 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
12/12/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
12/12/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
12/12/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
12/13/2007 | GERRY KOZIOL | WWM | REVIEW | Approved |