Permit Number - T07CM04571
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/11/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
01/11/2008 | VFLORES1 | WWM | REVIEW | Needs Review | |
12/07/2007 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
12/10/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Coordinate the design of the water service to the building as shown on shhets P-1 and A0. |
12/10/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
12/10/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
12/10/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | 1. PLANS SUBMITTED FOR PERMIT DO NOT MATCH MODEL PLAN 2. SUBMIT COMPLETE BUILDING DATA AS PER DSD REQUIREMENTS 3. JUSTIFY MODEL PLAN DETAIL 7/A-3 AND ASSUMED PROPERTY LINE NOTE PAGE A-1 W/ REFERENCE TO TABLE 705.4 |
12/10/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | The combined demand for 200 fixture units (100 Fixture units for each tenant space) is 65 GPM which is too great for a 1-1/2" meter. |
12/11/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/12/2007 | DAVE MANN | FIRE | REVIEW | Denied | Water design and fire service cannot meet design criteria in model plan. Fire hydrant required per IFC 508. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/11/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |