Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T07CM04571
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/11/2008 VFLORES1 WWM REVIEW Needs Review
12/07/2007 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/10/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Coordinate the design of the water service to the building as shown on shhets P-1 and A0.
12/10/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/10/2007 STEVE SHIELDS ZONING REVIEW Approved
12/10/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved 1. PLANS SUBMITTED FOR PERMIT DO NOT MATCH MODEL PLAN
2. SUBMIT COMPLETE BUILDING DATA AS PER DSD REQUIREMENTS
3. JUSTIFY MODEL PLAN DETAIL 7/A-3 AND ASSUMED PROPERTY LINE NOTE PAGE A-1 W/ REFERENCE TO TABLE 705.4
12/10/2007 ROBERT SHERRY WATER REVIEW Denied The combined demand for 200 fixture units (100 Fixture units for each tenant space) is 65 GPM which is too great for a 1-1/2" meter.
12/11/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/12/2007 DAVE MANN FIRE REVIEW Denied Water design and fire service cannot meet design criteria in model plan.

Fire hydrant required per IFC 508.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2008 VFLORES1 OUT TO CUSTOMER Completed