Permit Number: T07CM04567
Parcel: 14117007Q

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM04567
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. COMMENTS FROM THE PREVIOUS 3 DENIAL REVIEWS HAVE NOT BEEN MET: "STRUCTURAL DETAILS AND CALCULATIONS ARE REQUIRED FOR THE FIVE ROOF TOP MOUNTED MECHANICAL UNITS". THE TRUS JOIST PACKAGE SENT WITH THIS PROJECT FOR REVIEW LISTS INCORRECT MECHANICAL POINT LOADS AT INCORRECT LOCATIONS. TRUS JOISTS INDICATED ARE INCORRECT SPAN LENGTHS. RESUBMIT PERTINENT CALCULATIONS WITH CORRECT MECHANICAL LOADS.
2. WITH THE NEXT REVIEW, INCLUDE THE STRUCTURAL DRAWINGS PROVIDED BY SCHNEIDER & ASSOCIATES. ARCHITECTURAL DRAWINGS INDICATE STEEL ROOF JOISTS, WHILE THE TRUS JOIST PACKAGE SENT INDICATES WOOD.
03/24/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. (see sheet C1)
2. Comment not addressed. The applicable energy code for all projects is the 2006 International Energy Efficiency Code with Local Amendments. (see detail 4/P1)
3. Comment not addressed. Provide water isometrics and waste and vent isometrics for the scullery area of the kitchen. Reference: Section 103.2.3, UPC 2006.
4. Comment not addressed. Show how the reduced pressure zone backflow assemblies are drained. Reference: Section 304.0, UPC 2006.
5. Comment not addressed. Based on the submitted water calculations, a ½" water supply to a water closet is undersized. Reference: Section 610.1, UPC 2006.
6. Comment not addressed. Provide a floor drain in the kitchen. Reference Sections 411.2.2 and 704.3, UPC 2006.
7. Comment not addressed. Revise the size of the main natural gas pipe immediately downstream of the gas meter to comply with Section 1217.1, UPC 2006. Also, indicate the size of the gas manifold serving the fryers and range.
03/24/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide a copy of the approved shell drawings. Reference: Section 106.1.1, IBC 2006.
2. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
3. Comment not addressed. Provide the architectural details for the fire-rated chases noted on sheets M1 and M2. Note that the construction shown on detail 2/M2 is not an approved fire-rated assembly. Reference Section 106.3.1, IMC 2006
4. Comment not addressed. Provide justification for the basis for the population and required outside air quantities used in the ASHRAE 62.1-2004 calculations; Table 6-1 does not provide values for kitchens.
5. Comment not addressed. Provide structural calculations and details to show that the Type I hoods are supported from the building structure in accordance with Section 507.6, IMC 2006.
6. Comment not addressed. Provide information and control wiring diagrams to show that the operation of the Type I hoods and the hood exhaust fans comply with Section 507.2.1.1, IMC 2006.
7. Comment not addressed. Provide a non-absorbent, non-combustible, cleanable surface (e.g. a sheet of stainless steel) between the hood and the gypsum board behind the hood. Reference: Section 507.9, IMC 2006.
04/04/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved