Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04567
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/14/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NEED STRUCTURAL DETAILING AND CALCULATIONS FOR MECHANICAL UNITS ON ROOF (5 OF THEM) |
01/15/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/16/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
01/17/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
01/28/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04567 1/28/08 Please account for the full 38.2 MCA on the schedule for Panel A. High phase appears overloaded. Suggest that panel be rebalanced. Reference NEC 220.50, 430.24, and 440.7. |
01/29/2008 | GBONILL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
01/29/2008 | GBONILL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review |