Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM04567
Parcel: 14117007Q

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04567
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. NEED STRUCTURAL DETAILING AND CALCULATIONS FOR MECHANICAL UNITS ON ROOF (5 OF THEM)
01/15/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/16/2008 DAVE MANN FIRE REVIEW Approved
01/17/2008 GERRY KOZIOL WWM REVIEW Approved
01/28/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04567 1/28/08

Please account for the full 38.2 MCA on the schedule for Panel A. High phase appears overloaded. Suggest that panel be rebalanced. Reference NEC 220.50, 430.24, and 440.7.
01/29/2008 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review
01/29/2008 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review