Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04552
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/06/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/06/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/06/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04552 12/6/07 1. Provide panel and circuit for all new electrical loads. 2. Provide lighting fixture schedule on plans. 3. Demonstrate compliance with the 2006 IECC. 4. Provide panel schedule with load calculations for panel and feeder. |
| 12/06/2007 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/10/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/10/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/10/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/10/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/10/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/10/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |